ETC offers a
range of dedicated self-checking pressure and temperature
sensors for use as part of an ETC6000 system.
The ETC1021 Gas Pressure Sensor is installed between
the two gas isolating valves on the gas train. Once installed
the sensor can be used as part of the gas valve proving
system and can provide high and low level alarm and interlock
functions. Because the sensor is self-checking, the need
for mechanical pressure switches in eliminated.
The ETC1030/1034 & ETC1040/1044 are self-checking
steam pressure and temperature sensors. These provide
the measured value of the heating medium within the boiler
so that control can be achieved locally using internal
PID functions to vary the firing rate of the boiler and
position the servo motor drives throughout the chosen
profile. If an ETC self-checking pressure sensor is used
to provide the boiler high-limit lockout then a pressure
switch is not required.
Other functions such as alarm thresholds and warming
limits can also be assigned by adjusting parameters within
the main ETC6000 series controller. |